Datasheet Content
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE SK070045_A_en
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE
G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
Light-oil burners at two steps pressure.
They are composed by: aluminium frame, protection cover with noise reduction plate, combustion head with
micrometric adjustment, high flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
operations of setting and maintenance.
In the versions R preheater with control of temperature for soft and sicure ignitions also at low temperatures.
Complete of connector 7 poles, flange and gasket for installation on boiler, nozzle, flexible pipes, line filter.
Fig. 1 G 1.22R - G 1.22
Fig. 2 G 2.22R MAXI - G 2.22 MAXI
G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE SK070045_A_en
TECHNICAL DATA G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
MODEL G 1.22R G 1.22 G 2.22R G 2.22
MAXI MAXI
Flow min. 1st st. / min. 2nd st. - max. 2nd st. * [kg/h] 1.4/2.0-5.0 2.2/4-9.8
Thermal power min. 1st st. / min. 2nd st. - max. 2nd st. * [Mcal/h] 14.3/20.4-51 22.4/40.8-99.9
Thermal power min. 1st st. / min. 2nd st. - max. 2nd st. * [kW] 16.6/23.7-59.2 26/47.3-116
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two steps pressure
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [W] 220 130 250 140
Fan motor [W] 100 100 100 100
Nominal current absorption [A] 1 0.6 1.1 0.7
Pre-heater [W] 30-110 - 30-110 -
Power supply: 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness min. - max. ** [dBA] 57-59 57-59 59-61 59-61
Burner weight *** [kg] 10 10 10 10
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonorous pressure in the combustion laboratory, with burner on operation on beta boiler to 1m of distance (UNI EN ISO 3746).
*** For burner with iron cover (F) add 2 kg to the weight.
OPERATING RANGE DIAGRAM G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
Fig. 3 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE SK070045_A_en
DIMENSIONS [MM]
Fig. 4 Dimensions G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
MODEL A B C D E F G H I
G 1.22 - G 1.22R 157 170 275 80 265 210 15 150 150
G 2.22 MAXI - G 2.22R MAXI 157 170 275 90 265 210 15 150 150
* See "flame tube length"
BOILER PLATE
** Suggested dimension of connection between burner
and generator.
Fig. 5 Boiler plate
MODEL L min L ** L max M N min N ** N max
G 1.22 - G 1.22R mm 130 150 170 M8 90 110 130
G 2.22 MAXI - G 2.22R MAXI mm 130 150 170 M8 100 110 130
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL ***
G 1.22 - G 1.22R mm 112 152
G 2.22 MAXI - G 2.22R MAXI mm 107 147
*** For different flame lengths, please contact our Technical-Sales Department.
G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE SK070045_A_en
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Light-oil burners at two steps pressure.
DETAILED SPECIFICATION
Light-oil burners at two steps pressure, composed by:
• Aluminium frame;
• Combustion head with micrometric adjustment, high flame stability and low emissions;
• Protection cover with noise reduction plate;
• Flange and insulating gasket for fixing at boiler;
• Single-phase power supply;
• Photoresistance for flame detection;
• IP 40 electric protection level;
• Hydraulic system of regulation combustive air on the two stages of flame.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2014/68/EU Directive M.D.;
• 97/23/CE Directive P.E.D.;
• Reference rules: EN267 (liquid fuel) - EN746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• 7-poles plug for the electrical connections;
• Flexible hoses for connection;
• Line filter;
• Isomart gasket;
• Nozzle;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
G 1.22R - G 1.22 - G 2.22R MAXI - G 2.22 MAXI