Datasheet Content
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
SK070003_A_gb
ORMODULATING
BRUCIATORIDIGASOLIOBISTADIO
PROGRESSIVI
OMODULANTI
FGP50/MEVO
Light-oilburnerstwostagesprogressiveormodulatingoperation(ifequippedwithadditionofoptional
modulationkitPIDandprobe;toguaranteeanidealproportionalityofthepowersuppliedtothethermal
load).
Composedby:fanathighpressurisationatreversebladesandcombustionheadwithadjustmentathigh
efficiencyandhighflamestability.
Compactoveralldimensionsanddispositionrationalizedofthecomponentswithaccessibilityfacilitatedfor
theoperationsofsettingandmaintenance.
Completeofnozzle,flexiblepipesandlinefilter.
Completeofflangeandgasketforinstallationongenerator.
Fig. 1 FGP50/MEVO
FGP50/MEVO
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
SK070003_A_gb
ORMODULATING
TECHNICALDATAFGP50/MEVO
MODEL FGP50/MEVO
Thermalpowermin.1°st./min.2°st.-max.2°st.* [Mcal/h] 107/204-542
Thermalpowermin.1°st./min.2°st.-max.2°st.* [kW] 124/237-630
LIGHT-OILflowmin.1°st./min.2°st.-max.2°st.* [kg/h] 10.5/20-53
Fuel: LIGHT-OIL1.5°Eat20°C=6.2cSt=35secRedwoodN°1
Intermittedworkingoperation(min.1stopevery24hours)twostagesprogressiveormodulating
Environmentalconditionsoperation/storage: -15...+40°C/-20...+70°C,rel.humiditymax.80%
Max.temperaturecombustionair [°C] 60
Nominalelectricpower [kW] 1.1
Fanmotor [kW] 0.55
Pumpmotor [kW] 0.37
Nominalfanmotorcurrentabsorption [A] 1.4
Nominalpumpmotorcurrentabsorption [A] 1.2
Nominalauxiliaryabsorption [A] 0.6
Powersupply: 3~400V,1/N~230V-50Hz
Electricprotectiondegree: IP44
* Referenceconditions:Environmenttemperature20°C-Barometricpressure1013mbars-Altitude0metre(sealevel).
OPERATINGRANGEDIAGRAMFGP50/MEVO
<mbar> 13
11
9
7
5
3
)*30(92
1
-1
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 <kW>
Fig. 2 X=ThermalpowerY=Pressioninthecombustionchamber
ThefiringrateshasbeenobtainedbasedontestboilersinaccordancewithEN267standardsandareindicativeofmatchingtheburnertothe
boiler.Forthecorrectoperationoftheburner,combustionchamberdimensionsmustbeinaccordancewithcurrentregulation.Incaseofnon-
compliance,contactthemanufacturer.
FGP50/MEVO
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
SK070003_A_gb
ORMODULATING
DIMENSIONS[MM]
O
A B
F
P D
E
TC - TL * C
Fig. 3 DimensionsFGP50/MEVO
MODEL A B C D E F O P
FGP50/MEVO 329 274 746 150 416.5 100 207 200
C2:Overalldimensionwiththeburneroutinpositionofmaintenance.
* see"flametubelength"
FGP50/MEVO
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
SK070003_A_gb
ORMODULATING
BOILERPLATE
* Suggesteddimensionofconnectionbetweenburner
andgenerator.
Fig. 4 Boilerplate
MODEL M N min N max Lmin L* Lmax
FGP50/MEVO mm M10 205 226 160 160 180
FLAMETUBELENGTH
Flametubelengthmustbeselectedbasedonthespecificationssuppliedbyboilermanufacturerand,inanycase,it
mustbegreaterthanthethicknessoftheboilerdoorincludeditsinsulation.
Incaseofboilerswithflameinversionorfrontfluecombustionchambers,itisnecessarytoinsulatetheareabetween
theflametubeandfrontdoorwithrefractorymaterial.Thisprotectionmaterialmustnotimpedeflametube
extraction.
MODEL TC TL **
FGP50/MEVO mm 250 335
**Fordifferentflamelengths,pleasecontactourTechnical-SalesDepartment.
FGP50/MEVO
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
SK070003_A_gb
ORMODULATING
BURNERSIGNALDESCRIPTION
Inthepicturebelowthereareindicatedallthesignalationpresentontheburner:
2 1
Fig. 5 Burnersignaldescription
LEGEND
1) ON/OFFbutton
2) Resetfromlockoutbutton+statuslamp
The multicolor signal lamp in the lockout reset button (pos.2) is the key indicating element for visual diagnostics
and interface diagnostics.
In normal operation, the different operating states are indicated in the form of color codes; please refer to
electrical device handbook supplied with the present instructions.
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
By pressing the lockout reset button (pos.2) for more than 3 seconds, the visual diagnostics of the cause of fault
can be activated; please refer to electrical device handbook supplied with the present instructions.
For close the diagnostics mode and for switch on the burner again, it is necessary to reset the burner control.
Press the lockout reset button (pos.2) for about 1 second (<3 seconds).
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
For reset the control box press the lockout reset button (pos.2) for about 1 second (<3 seconds).
FGP50/MEVO
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
SK070003_A_gb
ORMODULATING
PRODUCTSPECIFICATION
SHORTDESCRIPTION
Light-oilburnerstwostagesprogressive(hi-lowflame)ormodulating(PIDfullymodulating)ifequippedwith
additionofoptionalmodulationkitandprobe.
DETAILEDSPECIFICATION
Light-oilburnertwostagesprogressive(hi-lowflame)ormodulating(PIDfullymodulating)ifequippedwithaddition
ofoptionalmodulationkitandprobe;composedby:
• Fanathighpressurisationatreverseblades;
• Combustionheadwithadjustmentathighperformanceandelevatedflamestability;
• Flangeandinsulatinggasketforfixingatboiler;
• Three-phasepowersupply;
• Photodiodeforflamedetection;
• IP44electricprotectionlevel;
• Servomotorforairshutterandforthepressureregulator;
• Easyextractionofcombustionheadwithoutgetofftheburnersbybolier;
• Maximumlight-oilpressureswitchtostoptheburnerincaseofthelight-oilpressureonthereturnishigherthenthesetpoint
value;
• Safetyairpressureswitchtostoptheburnerinlock-out(bystoppingthepumpmotor)incaseoffailedoranomalousfan
operation;
• Dedicatedmotorfortheactivationofthelight-oilpump;
• Setupfortheadditionalspecifickitthattransformsburneroperationasmodulatingi.e.themodulatingkitallowstosupply
anypowerbetweentheminimunandthemaximumvaluebasedoninstantaneousloadingrequest.
CONFORMINGTO:
• CErules;
• 2014/30/UEDirectiveE.M.C.;
• 2014/35/UEDirectiveL.V.;
• 2006/42/CE-2006/42/EG-2006/42/ECDirectiveM.D.;
• DirectivePED 2014/68/UE (ART.4,PAR.3);
• Referencerules:EN267(liquidfuel)-EN746-2(industrialthermoprocessingequipment).
STANDARDEQUIPMENT
• Flexible hoses for connection;
• Line filter;
• Isomart gasket;
• Nozzle;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Powermodulatingkitsfortemperatures;
• Powermodulatingkitsforpressures;
• Temperatureprobe0°C-400°C(PT100a0°C);
• Temperatureprobe0°C-350°C(Jprobe);
• Temperatureprobe0°C-1200°C(Kprobe);
• Pressureprobe0-3bar,0-6bar.0-16bar,0-20bar,0-30bar;
• Noiseprotection.
Theillustrationsanddatahereshownareindicative.F.B.R.BruciatoriS.r.l.reservestherighttobring,withoutanyobligationofwarning,anychangesthatwouldbeappropriatetothecontinuingdevelopmentoftheirproducts.
FGP50/MEVO