| Cable Type | two-wire thermoplastic |
| Sensor Type | photoresistor (flame sensor) |
| Qrb1a Mounting | fixed with bracket, guidance groove and cam for vibration protection |
| Qrb1b Mounting | soft plastic sleeve with sealing lips and retention lips, guidance spring |
| Mounting Options | with/without soft plastic sleeve, with/without bracket/collar |
| Measurement Method | probe current measurement |
| Flame Type Monitored | yellow oil flames |
| Maintenance Cleaning | clean cloth only, no burner aerosol sprays |
| Iso 9001 Certification | 2000 (Cert. 00739) |
| Iso 14001 Certification | 1996 (Cert. 38233) |
| Cable Routing Requirement | separate from other cables, especially ignition cable |
| Compatible Safety Controls | LAL..., LOA..., LMO... |
| Signal Quality Requirement | minimum interference and signal loss |
| Qrb1 Bracket Hole Spacing 1 | 21 mm |
| Qrb1 Bracket Hole Spacing 2 | 36 mm |
| Response Sensitivity Options | normal or elevated |
| Electromagnetic Compatibility Directive | 89/336/CEE |