Datasheet Content
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE (LX SK070063_B_en
SERIES) GX3-X4-X5.22-LX
LIGHT-OILBURNERSATTWOSTEPSPRESSURE(LXSERIES)
GX3.22-LX-GX4.22-LX-GX5.22-LX
Light-oilburnersattwostepspressure-LowNOx(NOx<120mg/kWh).
Theyarecomposedby:aluminiumframe,protectioncoverwithnoisereductionplate,combustionheadwith
micrometricadjustment,highflamestabilityandlowemissions.
Compactoveralldimensionsanddispositionrationalizedofthecomponentswithaccessibilityfacilitatedforthe
operationsofsettingandmaintenance.
Completeofconnector7polesforpowersupply,connector4polesfor2ndstagemodulation,flangeandgasketfor
installationonboiler,nozzle,flexiblepipes,linefilter.
Fig. 1 G X3.22-LX
Fig. 2 G X4.22-LX Fig. 3 GX5.22-LX
G X3.22-LX - G X4.22-LX - G X5.22-LX
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE (LX SK070063_B_en
SERIES) GX3-X4-X5.22-LX
TECHNICAL DATA G X3.22-LX - G X4.22-LX - G X5.22-LX
MODEL G X3.22-LX G X4.22-LX G X5.22-LX
Flow min.1°st. / min. 2°st. - max. 2°st. * [kg/h] 4.7/6.5-15 7.6/10-20 10.7/14-33
Thermal power min.1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 48/66-153 77.5/102-204 109/143-337
Thermal power min.1°st. / min. 2°st. - max. 2°st. * [kW] 56/77-178 90/118-236 127/166-391.4
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
NOx [mg/kWh] < 120:class 3 (EN267)
Intermitted working operation (min. 1 stop every 24 hours) two steps pressure
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [W] 220 250 600
Fan motor [W] 150 200 450
Nominal current absorption [A] 1 1.1 2.7
Power supply: 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness min. - max. ** [dBA] 66-66 67-68 71-72
Burner weight *** [kg] 14 14 25
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonorous pressure in the combustion laboratory, with burner on operation on beta boiler to 1m of distance (UNI EN ISO 3746).
*** For burner with iron cover (F) add 5 kg to the weight.
OPERATING RANGE DIAGRAM G X3.22-LX - G X4.22-LX - G X5.22-LX
Fig. 4 X = Thermal power Y = Pression in the combustion chamber
G X3.22-LX - G X4.22-LX - G X5.22-LX
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE (LX SK070063_B_en
SERIES) GX3-X4-X5.22-LX
Fig. 5 X = Flow Y = Pression in the combustion chamber
Fig. 6 X = Flow Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
G X3.22-LX - G X4.22-LX - G X5.22-LX
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE (LX SK070063_B_en
SERIES) GX3-X4-X5.22-LX
DIMENSIONS [MM]
Fig. 7 Dimensions
MODEL A B C D E F G H I L min L ** L max M N min N ** N max
G X3.22-LX 182 192 318 110 306 248 17 200 200 160 170 226 M10 120 130 140
G X4.22-LX 210 218 400 133 461 310 18 200 200 205 220 226 M10 140 150 180
G X5.22-LX 210 218 400 133 461 310 18 200 200 205 220 226 M10 140 150 180
* See "flame tube length".
** Suggested dimension of connection between burner and generator.
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL ***
G X3.22-LX mm 130 250
G X4.22-LX mm 215 335
G X5.22-LX mm 215 335
*** For different flame lengths, please contact our Technical-Sales Department.
G X3.22-LX - G X4.22-LX - G X5.22-LX
LIGHT-OIL BURNERS AT TWO STEPS PRESSURE (LX SK070063_B_en
SERIES) GX3-X4-X5.22-LX
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Light-oil burners at two steps pressure - Low NOx (NOx < 120 mg/kWh).
DETAILED SPECIFICATION
Light-oil burners at two steps pressure - Low NOx (NOx < 120 mg/kWh), composed by:
• Aluminium frame;
• Combustion head with micrometric adjustment, high flame stability and low emissions;
• Protection cover with noise reduction plate;
• Flange and insulating gasket for fixing at boiler;
• Single-phase power supply;
• UV scanner for flame detection;
• IP 40 electric protection level;
• Hydraulic system of regulation combustive air on the two stages of flame.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2006/42/UE Directive M.D.;
• 2014/68/UE (ART.4,PAR.3); Directive P.E.D.;
• Reference rules: EN267 (liquid fuel) - EN746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Connector4and7polesforelectricalconnections;
• Flexiblehosesforconnection;
• Linefilter;
• Isomartgasket;
• Nozzle;
• Flangewithinsulatinggasket;
• Burnernameplate;
• Warranty;
• Instructionhandbookforinstallation,useandmaintenance.
Theillustrationsanddatahereshownareindicative.F.B.R.BruciatoriS.r.l.reservestherighttobring,withoutanyobligationofwarning,anychangesthatwouldbeappropriatetothecontinuingdevelopmentoftheirproducts.
G X3.22-LX - G X4.22-LX - G X5.22-LX