LIGHT-OIL BURNERS
SK070090_C_en
TWO STAGES PROGRESSIVE OR MODULATING
FGP 75/M - FGP 100/M EVO - FGP 130/M EVO - FGP 160/M
Burners for light-oil two stages progressive (hi-low flame) or modulating (PID fully modulating) if equipped with
addition of optional modulation kit and probe.
Composed by: air blower at high pressurisation and combustion head with adjustment at high efficiency and high
flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
easy setting and maintenance.
Complete of nozzle, flexible pipes and line filter.
Complete of flange and gasket for installation on generator.
Fig. FGP 130/M EVO
FGP 75/M - FGP 100/M EVO - FGP 130/M EVO - FGP 160/M
LIGHT-OIL BURNERS
SK070090_C_en
TWO STAGES PROGRESSIVE OR MODULATING
TECHNICAL DATA FGP 75/M - FGP 100/M EVO
MODEL FGP 75/M FGP 100/M EVO
Thermal power min. 1°st. /min. 2°st. - max. 2°st. * [Mcal/h] 178/357-816 164.2/408-1020
Thermal power min. 1°st. /min. 2°st. - max. 2°st. * [kW] 207/415-949 190/474-1186
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 17.5/35-80 16.1/40-100
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15...+40°C/-20...+70°C,rel. humidity max.80%
Max. temperature combustion air [°C] 60 60
Nominal electric power [kW] 2.2 2.4
Fan motor [kW] 1.5 1.5
Pump motor [kW] 0.55 0.75
Nominal fan motor current absorption [A] 3.4 4.5
Nominal pump motor current absorption [A] 1.6 1.6
Nominal auxiliary absorption [A] 0.82 0.82
Power supply: 3~400V,1/N~230V-50Hz
Electric protection degree: IP40 IP40
Noiseness min. - max. ** [dBA] 78-82.5 82-83.6
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law).
FGP 75/M - FGP 100/M EVO - FGP 130/M EVO - FGP 160/M
LIGHT-OIL BURNERS
SK070090_C_en
TWO STAGES PROGRESSIVE OR MODULATING
OPERATING RANGE DIAGRAM FGP 75/M
[mbar]
FGP 75/M
[kW]
Fig. X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
OPERATING RANGE DIAGRAM FGP 100/M EVO
[mbar]
[kW]
Fig. X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
FGP 75/M - FGP 100/M EVO - FGP 130/M EVO - FGP 160/M
LIGHT-OIL BURNERS
SK070090_C_en
TWO STAGES PROGRESSIVE OR MODULATING
TECHNICAL DATA FGP 130/M EVO
MODEL FGP 130/M EVO
Thermal power min. 1°st. /min. 2°st. - max. 2°st. * [Mcal/h] 289/612-1326
Thermal power min. 1°st. /min. 2°st. - max. 2°st. * [kW] 336/712-1542
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 28.3/60-130
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15...+40°C/-20...+70°C,rel. humidity max.80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 3
Fan motor [kW] 2.2
Pump motor [kW] 0.75
Nominal fan motor current absorption [A] 4.35
Nominal pump motor current absorption [A] 1.6
Nominal auxiliary absorption [A] 0.82
Power supply: 3~400V,1/N~230V-50Hz
Electric protection degree: IP40
Noiseness min. - max. ** [dBA] 78-82.5
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law).
OPERATING RANGE DIAGRAM FGP 130/M EVO
[mbar] 17
15
13
11
9
7
5
3
1
-1
0 200 400 600 800 1000 1200 1400 1600 1800 2000
[kW]
Fig. X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
FGP 75/M - FGP 100/M EVO - FGP 130/M EVO - FGP 160/M
LIGHT-OIL BURNERS
SK070090_C_en
TWO STAGES PROGRESSIVE OR MODULATING
TECHNICAL DATA FGP 160/M
MODEL FGP 160/M
Thermal power min. 1°st. /min. 2°st. - max. 2°st. * [Mcal/h] 374/765-1634
Thermal power min. 1°st. /min. 2°st. - max. 2°st. * [kW] 435/889-1900
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 36.7/75-160
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15...+40°C/-20...+70°C,rel. humidity max.80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 5
Fan motor [kW] 4
Pump motor [kW] 0.75
Nominal fan motor current absorption [A] 7.45
Nominal pump motor current absorption [A] 2
Nominal auxiliary absorption [A] 0.82
Power supply: 3~400V,1/N~230V-50Hz
Electric protection degree: IP40
Noiseness min. - max. ** [dBA] 84.4-85.4
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).