Datasheet Content
LIGHT-OIL BURNERS TWO STAGES PROGRESSIVE OR
SK070079_A_gb_350-450-550
MODULATING WITH ELECTRONIC CONTROL BOX
FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
Burners for light-oil two stages progressive (hi-low flame) or modulating (PID fully modulating) if equipped with
addition of optional modulation kit and probe.
Composed by: fan at high pressurisation and combustion head with adjustment at high efficiency and high
flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
operations of setting and maintenance.
The adoption of strong metal components makes the burner durable also in heavy duty conditions.
Complete of flange and gasket for installation on generator, nozzle, flexible pipes and line filter.
The actuators are independent and are managed directly by the electronic cam:
- one actuator for the air shutter
- one actuator for the light-oil modulator
The burners are equipped with an electronic microprocessor system, in addition there is a LCD display with
interactive configuration.
With the addition of optional accessories (probes) thanks to the most advanced systems for automatic
modulation, the burner constantly ensures the proper fuel / air ratio. The maximum efficiency of the returns in
each combustion point derived from the punctual adaptation of the thermal load to the heat requirements of the
burner at any instant of operation.
The fuel / combustion air curve, more extended, is fully exploited, guaranteeing excellent performance in terms of
accuracy and speed, even during the calibration phase. A microprocessor monitors the different stages of the
process and allows the correct repetition of the sequences of operation.
Some accessories are available, like: PC interface, VSD (inverter), Profibus, Modbus.
Fig. 1 FGP 450/M-EL
FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
LIGHT-OIL BURNERS TWO STAGES PROGRESSIVE OR
SK070079_A_gb_350-450-550
MODULATING WITH ELECTRONIC CONTROL BOX
CONTROL BOX LAMTEC BT3
Fig. 2 Control box Lamtec BT3
FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
LIGHT-OIL BURNERS TWO STAGES PROGRESSIVE OR
SK070079_A_gb_350-450-550
MODULATING WITH ELECTRONIC CONTROL BOX
TECHNICAL DATA FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
MODEL FGP 350/M-EL FGP 450/M-EL FGP 550/M-EL
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 46/140-350 53/160-450 66/200-550
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 460/1400-3500 530/1600-4500 660/2000-5500
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 534/1660-4151 615/1898-5337 766/2372-6523
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60 60 60
Nominal electric power [kW] 12 14 21
Fan motor [kW] 9 11 18.5
Pump motor [kW] 2.2 2.2 2.2
Nominal motor current absorption [A] 19 21.7 36
Nominal auxiliary absorption [A] 0.6 0.6 0.6
Power supply: 3~400V, 1N~230V - 50Hz
Electric protection degree: IP 40 IP 40 IP 40
Noisiness ** min. - max. [dB(A)] 86-86 88-89 89-90
Burner weight [kg] 230 240 287
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonourous pressure in the combustion lab, with funcional burner on beta boiler in a distance of 1 m (UNI EN ISO 3746).
OPERATING RANGE DIAGRAM FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
23
19
15
11
7
3
FGP 350/M FGP 450/M FGP 550/M
-1
100 1100 2100 3100 4100 5100 6100 7100
Fig. 2 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
LIGHT-OIL BURNERS TWO STAGES PROGRESSIVE OR
SK070079_A_gb_350-450-550
MODULATING WITH ELECTRONIC CONTROL BOX
DIMENSIONS [MM]
20 H
G
D
H
F
E C B A
Fig. 3 Dimensions FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
MODEL A B C D E F G H
FGP 350/M-EL 615 600 537 334 1035 480 245 490
FGP 450/M-EL 615 600 562 380 1035 480 245 490
FGP 550/M-EL 615 660 562 380 1035 480 245 490
BOILER PLATE
* Suggested dimension of connection between burner and
generator
Fig. 4 Boiler plate
MODEL M N min N* N Max L min L* L max
FGP 350/M-EL mm M14 552 552 580 350 350 450
FGP 450/M-EL mm M14 552 552 580 390 390 450
FGP 550/M-EL mm M14 552 552 580 390 410 450
FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL
LIGHT-OIL BURNERS TWO STAGES PROGRESSIVE OR
SK070079_A_gb_350-450-550
MODULATING WITH ELECTRONIC CONTROL BOX
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Light-oil burners two stages progressive (hi-low flame) or modulating (PID fully modulating) if equipped with
addition of optional modulation kit and probe.
DETAILED SPECIFICATION
Light-oil burner two stages progressive (hi-low flame) or modulating (PID fully modulating) if equipped with addition
of optional modulation kit and probe; composed by:
• Fan at high pressurisation;
• Combustion head with adjustment at high performance and elevated flame stability equipped with inox steel blast tube and
steel flame disc;
• Flange and insulating gasket for fixing at boiler;
• Three-phase power supply;
• Photoresistance for flame detection;
• IP 40 electric protection level;
• Electronic control box for control and supervision of burner;
• One servomotor for air shutter;
• One servomotor for the fuel pressure regulator;
• Easy extraction of combustion head without get off the burners by bolier;
• Maximum light-oil pressure switch to stop the burner in case of the light-oil pressure on the return is higher then the set
point value;
• Safety air pressure switch to stop the burner in case of failed or anomalous fan operation;
• Mobile shutter with total closure when idle for minimize the energetic losses related at boiler cooling;
• Dedicated electric motor for light-oil pump;
• LCD display with interactive configuration;
• Set up for the additional specific kit that transforms burner operation as modulating i.e. the modulating kit allows to
supply any power between the minimun and the maximum value based on instantaneous loading request.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2014/68/EU Directive M.D.;
• 97/23/CE Directive P.E.D.;
• Reference rules: EN267 (liquid fuel) - EN746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Flexible hoses for connection;
• Line filter;
• Isomart gasket;
• Nozzle;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Power modulating kits for temperatures;
• Power modulating kits for pressures;
• Temperature probe 0°C-400°C (PT 100 a 0° C);
• Temperature probe 0°C-1200°C (K probe);
• Pressure probe 0-3 bar, 0-6 bar. 0-16 bar, 0-20 bar, 0-30 bar;
• Noise protection.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products.
FGP 350/M-EL - FGP 450/M-EL - FGP 550/M-EL