We ship to the Philippines — door-to-door, customs and logistics handled by 3G Electric

Pactrol 3G-CBM-04702

Pactrol 3G-CBM-04702 — Technical Specifications

Pactrol Microgas P25F FTL/V24 427001/V24

Technical Specifications

ParameterValue
Ce CertifiedYes
Spark Energy> 4 mJ (W.H.I.T.B.)
Internal Fuse2 A HPC (20 mm)
Pre Purge Time1.5–50 seconds
Supply Voltage230 V + 10% - 15%
Aps Type Options2 or 3 terminal or not present
Humidity Maximum90% RH
Supply Frequency50–60 Hz (± 3 Hz)
Power Consumption15 VA
Pre Ignition Time1.0–50 seconds
Spark Gap Tolerance2.5–4.5 mm
Lockout Type Optionsvolatile or non-volatile
Open Circuit Voltage15 kV minimum (30 pf loading)
Relay Contact Rating1 A Inductive 0.6 pf @ 230 V ac
Appliance Type Optionsfanned or atmospheric
Certification StandardEN 298:2003
Flame On Response Time1 second max
Ambient Temperature Range-10°C to 70°C
Flame Detection PrincipleRectification
Supply Phase RelationshipSensitive to Live and Neutral phase reversal
Total Maximum Load Current2 A
External Transformer Rating230 V:230 V 2 VA
Number Of Ignition Attempts1–5
Minimum Flame Current Required1 µA @ 230 V ac supply
Flame Detector Electrode ConfigurationDual or single probe ignition & detection

Physical & Shipping Data

Weight0.8 kg
Length150 mm
Width120 mm
Height100 mm
Country of OriginFrance

Downloads

Datasheet (PDF)