TYPES G.. OR.. Series 03N
AUTOMATIC CONTROL SYSTEMS FOR
OIL BURNERS APPLICATION
The electro-mechanical controllers of this series are
designed to control oil burners in non-permanent
applications.
These controllers are suitable for :
− monoblock burners
− power washers
− hot air generators
− steam boilers
− furnaces
Due to the models technical and constructive features and
to their variety they can be used also for the automation of
cookers, and of plants employing oil burners generally,
whether in domestic or industrial applications. These
controllers replace integrally the 03 electro-mechanical
series
FEATURES
Table 1 shows the main features of this series.
Other important features are:
− two independent safety contacts for valve driving
− electrical service life at max. declared load > 250.000
operations;
− Easy installation and connection.
TABLE 1
Lockout due to extraneous light (2)
Thermal range< 30kg/h Thermal range> 30kg/h FC7/. FC8/ photocells FC11/. FC13/.photocells
Single flame Dual flame preheater (1) Pre-ignition
G22 * * * * * *
GF2 * * * * *
GF3 * * * * *
OR1 * * * * * *
OR2 * * * * *
OR3 * * * * *
(1) Application is possible with appropriate connection
(2) Function is available only in controllers with 12V and
24V supply voltage and GF2 220V and 110V
13697_r00 1/5
CONNECTION
TECHNICAL DATA The connection bases type B and N can be provided to
connect the external components to the controller (see Fig.
Power supply : 220V 50/60Hz 2). Both bases are provided with screw terminals which
Upon request: 110V 50/60Hz allow a safe and easy connection. It’s advisable to use M4
24V dc and ac 50/60Hz screw for fastening purpose.
12V dc and ac 50/60Hz
Operating temperature -10°C ÷ +60°C
Protection degree (with base) IP 40
Times
– Pre-purge time (TV @ 20°C): 15/20 s
– Safety time (TS @ 20°C): 5/10 s
– Response time in case of flame failure: <1s
Power consumption (@220V-50Hz): 6,5 VA
(@12V/24V ): 1VA
Internal Fuse
– For 220V e 110V supply voltage: 6,3 A time-delay
– For 24V e 12V supply voltage: 10 A time-delay
External fuse
– For 220V e 110V supply voltage: 4 A fast-blow
– For 24V e 12V supply voltage: 10 A fast-blow
Weight including connection base: about 240 g
Max. contacts rating (@220V): Imax Fig.2
– Thermostat: 6,0 A cosϕ > 0,4
– Motor: 2,0 A cosϕ > 0,4 ACCESSORIES
– Ignition transformer: 2,0 A cosϕ > 0,4 The following indications must be considered in order to
– EV1: 0,5 A cosϕ > 0,4 choose the suitable flame detector for the controller and
the application type:
– EV2: 0,5 A cosϕ > 0,4
– Preheater: 0,5 A cosϕ = 1,0 Controller Type Photocell
– Lockout signal: 1,0 A cosϕ = 1,0 - G22, GF2, GF3
Max. contacts rating (@12V e 24V): Imax FC8/R 1,5..5,5 lux
– Thermostat: 10 A cosϕ > 0,4 Frontal side FC8/A 1,5..3,0 lux
– Motor: 4,0 A cosϕ > 0,4 FC8/V 5,5.. 10 lux
– Ignition transformer: 3,0 A cosϕ > 0,4
– EV1: 1,5 A cosϕ > 0,4 FC7/R 1,5..5,5 lux
– EV2: 1,5 A cosϕ > 0,4 Lateral side FC7/A 1,5..3,0 lux
– Lockout signal: 1,0 A cosϕ = 1,0 FC7/V 5,5…10 lux
- OR1, OR2, OR3
CONSTRUCTION Frontal and lateral side FC11/R* 1,5..6,5 lux
The plastic enclosure protects the controller against
mechanical damage caused by crash, tempering , dust and Frontal and lateral side FC13/R 1,5..6,5 lux
dirt of external ambient. An inbuilt fuse protects the FC13/A 1,5..3,0 lux
controller internal relays in case of short circuit on the
outputs (valves, fan and lockout signal); * The FC11/R is provided with a black plastic enclosure
only
The suffix indicates the colour of the photocell enclosure:
/R red
OVERALL DIMENSIONS /A blue
Fig1 shows the controller overall dimensions /V green
FC7 FC8 drilling plane FC13 drilling plane FC11 drilling plane
Base type dimensions h
B 99
N 98.3
Fig.1
Fig. 3 Fig. 4
2/5 13697_r00
The figures (Fig.3) show the types and fixing systems of CHECKING AT START
the available flame detectors. Before any ignition attempt make sure that the combustion
4 mm diameter screws are suggested To fix the flame chamber is free from oil, then make sure that:
detector. − if the starting attempt occurs with the flame detector
Core hitches and Strain relieves can be fitted on the sides obscured the controller performs a lockout at the end of
of the controllers enclosures and the connecting bases. safety time;
These accessories can be supplied upon request (see − if start up attempt occurs with extraneous light, the
Fig.5). controller proceeds to lockout within the time equivalent
to safety time (only in versions where this option is
available) ;
− when the flame detector is obscured in running position
the oil valve(s) is/are de-energized within 1 second, and
the controller goes to lockout after a recycle;
The intervention of regulators, limiters or safety devices
causes a shut down of the controller according to the
Fig.5 application type;
− Operating times and cycle are in compliance with the
INSTALLATION DIRECTIONS ones declared for the used controller type.
− The controllers are safety devices; guarantee and
responsibility of the manufacturer will be debarred if
the products are tempered with by the user;. OPERATION
− Make sure that a regulation shutdown occurs every 24 Once the thermostats are closed, the controller energizes
hours to allow the controller self-checking its efficiency the burner motor; in this phase the device proceeds to a
(non permanent operation systems). self-checking process of the flame detection and safety
− The controller must be connected and disconnected circuit. At the end of pre-purge time the output of the first oil
without power supply. valve is powered. If flame is detected, at the end of safety
− The controller can be mounted in any position. time, the controller de-energizes the ignition transformer
− Avoid exposure to dripping water. and goes to running position.
− A ventilated installation ambient and a quite low At the end of safety time, in the double stage controllers,
temperature ensure the longest life of the controller…