GAS BURNERS TWO STAGES PROGRESSIVE OR 073070_A_en
mod: GAS P130/MCE EL EVO
MODULATING WITH ELECTRONIC CONTROL BOX GAS P160/MCE EL
GAS P130/MCE EL EVO - GAS P160/MCE EL
Gas burners with electronic control box. Two stages progressive or modulating operation (if equipped with addition
of optional modulation kit PID and probe; to guarantee an ideal proportionality of the power supplied to the thermal
load).
Composed by: die-cast aluminum body, high pressurisation air blower and combustion head with adjustment at high
efficiency and high flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for easy
setting and maintenance.
Available in the versions METHANE (natural gas) or L.P.G. (to specify at the order) on demand specific versions for
town gas, coal gas or biogas.
Gas train completely assembled and tested; composed by working valve with flow adjustment, safety valve,
minimum gas pressure switch,valve proving system and gas filter + gas pressure stabiliser.
Complete of flange and gasket for installation on generator.
The servomotors are indipendent and managed directly from the electronic control box of the burner: one servomotor
for the gas modulator and one servomotor for the air shutter.
The burners are equipped with a display that allows to:
- adjust the operating parameters of the burner
- visualize the flame intensity
- adjust the operating curve of the burner (air / gas ratio)
With the addition of optional accessories (probes) thanks to the most advanced systems for automatic modulation in
mechanical or electronic version, the burner constantly ensures the proper gas / air ratio.
The maximum efficiency of the returns in each combustion point derived from the punctual adaptation of the thermal
load to the heat requirements of the burner at any instant of operation.
In the version with the electronic cam the fuel / combustion air curve, more extended, is fully exploited, guaranteeing
excellent performance in terms of accuracy and speed, even during the calibration phase.
A microprocessor monitors the different stages of the process and allows the correct repetition of the sequences of
operation.
Optional accessories: PID power modulator kit, probe, PC interface, VSD, O2 control, O2 + CO control, field bus
(profibus, modbus, profinet).
Fig. GAS P130/MCE EL EVO
GAS P130/MCE EL EVO - GAS P160/MCE EL
GAS BURNERS TWO STAGES PROGRESSIVE OR 073070_A_en
mod: GAS P130/MCE EL EVO
MODULATING WITH ELECTRONIC CONTROL BOX GAS P160/MCE EL
CONTROL BOX LAMTEC BT3
Fig. Control box Lamtec BT3
GAS P130/MCE EL EVO - GAS P160/MCE EL
GAS BURNERS TWO STAGES PROGRESSIVE OR 073070_A_en
mod: GAS P130/MCE EL EVO
MODULATING WITH ELECTRONIC CONTROL BOX GAS P160/MCE EL
TECHNICAL DATA AND OPERATING RANGE DIAGRAM GAS P130/MCE EL EVO
MODEL GAS P130/MCE EL EVO
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 206/612-1324
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 240/712-1540
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 24/71.5-155
Gas flow G31 (L.P.G.) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 9.3/27.6-59.8
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Min. pressure gas train D2"-S NATURAL GAS/L.P.G. ** [mbar] 52.4/28.2
Min. pressure gas train DN65-FS65 NATURAL GAS/L.P.G. ** [mbar] 29.9/21
Min. pressure gas train DN80-FS80 NATURAL GAS/L.P.G. ** [mbar] 27.4/18.4
Maximum pressure at the entry of valves (D2") [mbar] 360
Maximum pressure at the entry of valves (DN65 - DN80) [mbar] 500
Nominal electric power [kW] 2.4
Fan motor [kW] 2.2
Nominal motor current absorption [A] 4.35
Nominal auxiliary absorption [A] 0.7
Power supply: 3~400V, 1/N~230V-50Hz
Electric protection degree: IP 54
Noisiness *** min. - max. [dB(A)] 82-83
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law -
Control method class 3 - The measured sound pressure tolerance can be assumed to be ± 1 [dB (A)]).
GAS P130/MCE EL EVO - GAS P160/MCE EL
GAS BURNERS TWO STAGES PROGRESSIVE OR 073070_A_en
mod: GAS P130/MCE EL EVO
MODULATING WITH ELECTRONIC CONTROL BOX GAS P160/MCE EL
TECHNICAL DATA AND OPERATING RANGE DIAGRAM GAS P160/MCE EL
MODEL GAS P160/MCE EL
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 275/765-1647
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 320/890-1915
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 32.2/89.5-192
Gas flow G31 (L.P.G.) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 12.4/34.5-74.2
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Min. pressure gas train D2"-S NATURAL GAS/L.P.G. ** [mbar] 64.5/40.4
Min. pressure gas train DN65-FS65 NATURAL GAS/L.P.G. ** [mbar] 35.8/29.2
Min. pressure gas train DN80-FS80 NATURAL GAS/L.P.G. ** [mbar] 25.8/25.3
Maximum pressure at the entry of valves (D2") [mbar] 360
Maximum pressure at the entry of valves (DN65 - DN80) [mbar] 500
Nominal electric power [kW] 4.2
Fan motor [kW] 4
Nominal motor current absorption [A] 7.45
Nominal auxiliary absorption [A] 0.6
Power supply: 3~400V, 1/N~230V-50Hz
Electric protection degree: IP 54
Noisiness *** min. - max. [dB(A)] 84.3-86.6
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law -
Control method class 3 - The measured sound pressure tolerance can be assumed to be ± 1 [dB (A)]).
GAS P130/MCE EL EVO - GAS P160/MCE EL
GAS BURNERS TWO STAGES PROGRESSIVE OR 073070_A_en
mod: GAS P130/MCE EL EVO
MODULATING WITH ELECTRONIC CONTROL BOX GAS P160/MCE EL
16
GAS P130/MCE EVO EL
14
12
10
8
6
4
2
0
0 200 400 600 800 1000 1200 1400 1600 1800
Fig. X = Thermal power [kW] Y = Pression in the combustion chamber [mbar]
The firing rates has been obtained based on test boilers in accordance with EN676 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
16…