Datasheet Content
GAS BURNERS TWO STAGES PROGRESSIVE OR SK073067_A_en
mod: GAS P130/MCE EVO
MODULATING GAS P160/MCE
GAS P130/MCE EVO - GAS P160/MCE
Burners for gas two stages progressive (hi-low flame) or modulating (PID fully modulating) if equipped with
addition of optional modulation kit and probe.
Composed by: die-cast aluminum body, high pressurisation air blower and combustion head with adjustment at
high efficiency and high flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for easy
setting and maintenance.
Available in the versions METHANE (natural gas) or L.P.G. (to specify at the order) on demand specific versions for
town gas, coal gas or biogas.
Gas train completely assembled and tested; composed by working valve with flow adjustment, safety valve,
minimum gas pressure switch, valve proving system and gas filter + gas pressure stabiliser.
Complete of flange and gasket for installation on generator.
GAS P130/MCE EVO - GAS P160/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR SK073067_A_en
mod: GAS P130/MCE EVO
MODULATING GAS P160/MCE
TECHNICAL DATA GAS P130/MCE EVO - GAS P160/MCE
MODEL GAS P130/MCE EVO GAS P160/MCE
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 206/612-1324 275/765-1647
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 240/712-1540 320/890-1915
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 24/71.5-155 32.2/89.5-192
Gas flow G31 (L.P.G.) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 9.3/27.6-59.8 12.4/34.5-74.2
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL, I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60 60
Min. pressure gas train D2"-S NATURAL GAS/L.P.G. ** [mbar] 52.4/28.2 64.5/40.4
Min. pressure gas train DN65-FS65 NATURAL GAS/L.P.G. ** [mbar] 29.9/21 35.8/29.2
Min. pressure gas train DN80-FS80 NATURAL GAS/L.P.G. ** [mbar] 27.4/18.4 25.8/25.3
Max. pressure at the entry of valves (Pe. max) (D2") [mbar] 360 360
Max. pressure at the entry of valves (Pe. max) (DN65 - DN80) [mbar] 500 500
Nominal electric power [kW] 2.4 4.2
Fan motor [kW] 2.2 4
Nominal motor current absorption [A] 4.35 7.45
Nominal auxiliary absorption [A] 0.7 0.6
Power supply: 3~400V,1N~230V - 50Hz
Electric protection degree: IP 40 IP 40
Noisiness *** min. - max. [dB(A)] 82-83 84.3-86.6
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law -
method of control Class 3 - The tollerance of the measured pressure can be taken equal to ± 1 [dB(A)]).
GAS P130/MCE EVO - GAS P160/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR SK073067_A_en
mod: GAS P130/MCE EVO
MODULATING GAS P160/MCE
OPERATING RANGE DIAGRAMS
16
GAS P130/M CE EVO
14
12
10
8
6
4
2
0
0 200 400 600 800 1000 1200 1400 1600 1800
Fig. X = Thermal power [kW] Y = Pression in the combustion chamber [mbar]
The firing rates has been obtained based on test boilers in accordance with EN676 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
16
GAS P160/M CE
14
12
10
8
6
4
2
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200
Fig. X = Thermal power [kW] Y = Pression in the combustion chamber [mbar]
The firing rates has been obtained based on test boilers in accordance with EN676 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
GAS P130/MCE EVO - GAS P160/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR SK073067_A_en
mod: GAS P130/MCE EVO
MODULATING GAS P160/MCE
DIMENSIONS GAS P130/MCE EVO [mm]
320
40 183
211
320
O 209
320 229
20 510
320
TC-TL
240 343 148 B
C 803 - 1388**
A
Fig. Dimensions GAS P130/MCE EVO
GAS TRAIN A B C
** Overall dimension with the burner out in position of maintenance.
D2"-S 684 350 510
DN65-FS65 686 393 510 TC - TL: see "flame tube length"
DN80-FS80 740 433 550
DIMENSIONS GAS P160/MCE [mm]
320
40 183 211
320
O 209
320 229
20 510
320
401
240 402 148 B
C 803 - 1388**
A
Fig. Dimensions GAS P160/MCE
GAS TRAIN A B C
** Overall dimension with the burner out in position of maintenance.
D2"-S 684 350 510
DN65-FS65 686 393 510 TC - TL: see "flame tube length"
DN80-FS80 740 433 550
GAS P130/MCE EVO - GAS P160/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR SK073067_A_en
mod: GAS P130/MCE EVO
MODULATING GAS P160/MCE
BOILER PLATE
*** Suggested dimension of connection between
burner and generator.
Fig. Boiler plate
MODEL L min L*** L max M N min N max
GAS P130/MCE EVO mm 220 220 250 M14 340 368
GAS P160/MCE mm 220 220 250 M14 340 368
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door…