Datasheet Content
EU Declaration of Conformity
Guarantee of Product Quality
Type samples of the product detailed below, have been tested and examined by BSi, notified body
number 0086, and found to comply with the essential requirements of annex 1 of the European Gas
Appliance Directive (G.A.D.) Document: (2009/142/EC) up to 21st April 2018, then the Gas
Appliances Regulation (EU) 2016/426 thereafter.
This product has been designed using processes in accordance with: BS EN ISO 9001 and is
manufactured as Type-approved above, in accordance with: BS EN ISO 9001 attestation
procedures, which complies with the UK. Gas Appliance (Safety) Regulations 1995 1629.
Conformity with the BS EN ISO 9001 Quality System Surveillance requirements, as specified in
Annex 2/ part 3.3 of the above G.A.D. and Annex 3 / part 3.3 of the above G.A.R, is assured by BSi,
notified body number 0086.
Approval Information
Pactrol Controls declare that the DoC is issued under our sole responsibility and belongs to the
following product covered by this certificate:
Product: CSS2 PRTV 230 429103/V01
GAD Certificate No.: CE 620691
GAR Certificate No.: CE 686496
Harmonised Standards: EN298: 2012
OEM's and Appliance Designers
For correct Application and Installation instructions for the above control, refer to Pactrol Technical
Sheet No: 429100/II available from the address below.
Spares and Replacement Parts
Where this fitting is used as a replacement spare part for a gas appliance, it must be installed in
accordance with the servicing instructions issued by the appliance manufacturer.
Read the instructions before use. This control must be installed in accordance with the rules in force.
Signed on behalf of
Pactrol Controls Ltd.
Unit 3 Antler Court, 4291 03/V01/FC
Three Sisters Enterprise Park
Ashton in Makerfield, i 5
Wigan. WN4 8DU.
England. : : 06/03/2018
Telephone: +44(0)1942429240 L.Washbourn
Fax No.: +44(0)1942529241 R&D Manager
429103/VO01/FC
--- PAGE BREAK ---
Technical Specification
Supply Voltage:
Supply Frequency:
Phase Relationship:
Internal Fuse:
Power Consumption:
Protectlon degree:
Ambient temperature range:
Mounting position:
Inputs:
Lockout reset:
Loads specified as 230Vac (cos@ >=0.6):
Lockout Indicator:
Gas Valve 1:
Gas Valve 2:
Total maximum continuous load:
Lockout Type:
Lockout reset response time:
Lockout reset switch:
Wait time (Tw):
Ignition time (Ti):
Safety time 1 (Ts):
Pilot proving time (Tps):
Safety time 2 (Ts2):
Interpurge time :
Ignition attempts:
Ignition behaviour:
Spark Voltage
Spark frequency
Spark gap
Maximum length of HT leads:
Flame sensor type:
Electrode configuration:
Flame sensitivity:
Flame detector response time:
Max. length of detection lead:
Action on flame loss:
429103/VO1/FC
230 Vac
50/60 Hz
Phase sensitive (Neutral/Earth relationship required)
2AF HBC
<25W (electronics only)
IP40
-10° to +60°C
Not critical
230 Vac 50/60 Hz
Max. 0.5A @ 230 Vac 50/60 Hz
Max. 1A @ 230 Vac 50/60 Hz
Max. 1A @ 230 Vac 50 Hz
2A
Volatile
1.5s
Momentary action normally open connecting to N
12s
6s
6s
Os
Os
12s
1
Immediate Run (ign stops immediately upon flame detection)
>15kV @ 30pF load
25.00Hz
2.5- 4.5mm
1 metre
(Resistive suppression 1K @ HT end of lead recommended)
Flame ionisation rectification
Single, Dual, Triple
On = 1.5pA, Off = 1.0pA
Flame on = 1s max, Flame off = 0.5s
1 metre
Recyle
Page 2 of 4
--- PAGE BREAK ---
Wiring Diagram
H
detection circuit.
CSS2 xxTx
19 110 [11 112 113 114 [15 [16 |
7. —S
P0008 ~
f— J Triple Probe
P/No. 92576_2
Phase to Earth Bonding
In several countries, due to poor or non-existent neutral to earth bonding, or non-standard electrical
distribution systems, it is necessary to provide a reliable flame current return path for the flame
If the supply does not have an EARTH BONDED CONDUCTOR, or is THE EARTH IS DERIVED
FROM A CENTRE TAPPING BETWEEN TWO PHASES, then the following method of connection is
recommended:
F1 (uc)
Sized to match VA
rating of transformer
Phase 1
Incoming (Live)
Mains
Phase 2
Supply (Neutral) }
EARTH
429103/V01/FC
No Phase - Earth
relationship or Earth
is centre tapped
Appliance
Chassis
Isolating
Transformer
230V : 230V
<== LIVE
Supply
to
NEUTRAL FSC
Bond transformer
secondary to Earth
EARTH
The Transformer rating should be sufficient to power the FSC and its loads
(fan, gas valve and igniter), whilst maintaining an output regulation of + 5%
Typically, a SOOVA transformer is sufficient for a total FSC load of 2A,
Page 3 of 4
--- PAGE BREAK ---
Timing Diagram CSS2 PRTV 230 (429103/V01)
Flame LED
ignition
Tw Ti+ Ts Tps Ts2
125 | 6s Os Os
Tw = Wait time
Ti = Ignition time
Ts = 1st safety time
Tps = Pilot Stabilisation time
Ts2 = 2nd safety time
IIIT = flashing blue flame Led
Page 4 of 4
429103/VO1/FC
EC Type Approved - Fitting Certificate
DECLARATION OF CONFORMITY - GUARANTEE OF PRODUCT
QUALITY
Type samples of the product detailed below, have been tested and examined by GL Industrial Services, notified
body number 0087, and found to comply with the essential requirements of annex 1 of the European Gas
Appliance Directive (G.A.D.) Document:- (90/396/EEC).
This product has been designed in accordance with:- BS EN ISO 9001 and is manufactured as Type-approved
above, in accordance with :- BS EN ISO 9002 attestation procedures, which complies with the UK. Gas
Appliance (Safety) Regulations 1992 16/22
Conformity with the BS EN ISO 9000 Quality System Surveillance requirements, as specified in Annex 2 / part
3.3 of the above G.A.D., is assured by BSI, notified body number 0086.
CE- TYPE APPROVAL INFORMATION
Product covered by this certificate :- CSS2 PRTV01
Pactrol Part number 429103/V01
Pactrol design file X325
EC Product Identification No. :- C87BU07
Certificate No. :- EC-87/09/007
EN298 Classification :- ATCVXN
O.E.M.’s AND APPLIANCE DESIGNERS
For correct Application and Installation instructions for the above control, refer to Pactrol Installation
Instruction No: 429100/V01/II available from the address below.
SPARES AND REPLACEMENT PARTS
Consult ONLY the appliance manufacturers’ servicing instructions, and ensure that the correct control is
installed in accordance with them.
Signed on behalf of:- B.P.Faulkner Ref: 429103/V01/FC
Pactrol Controls Limited Development Director
Unit 3 Antler Court Issue: 1
Ashton-in-Makerfield
Wigan WN4 8DU Date: 12/11/09
England
Tel: +44 (0)1942 529240
Fax: +44 (0)1942 529241
Page 1 of 3
CSS2 : General Technical specifications
Supply voltage 230Vac + 10% / -15%
Supply frequency 50 / 60Hz
Phase relationship Phase sensitive - Earth bonding to Neutral supply required
Internal fuse 2A F
Power consumption <0.5VA
Loads at 0.6pf @ 230Vac:
Reset indicator 0.5A maximum
1st Stage gas valve 1.0A maximum (where fitted)
Main gas valve 1.0A maximum (where fitted)
Spark Output > 25kV into 30pF, 25 sparks per second
Total maximum load 2A
Flame detection principle Flame Ionisation rectification
Electrode configuration Single/Dual/Triple probe
Maximum length of detection lead 1 Metre
Protection degree IP40
Ambient temperature range -10°C to +60°C
Humidity 90% max. @ 40° C (non-condensing)
Mounting position Not critical
Wiring Diagram: 2 stage
Wiring Diagram: 1 stage
Page 2 of 3
CSS2 PRTV 01: Variant Details
Timing Diagram
Front Panel
CSS2 PRTV 01: Variant Specific Information
Gas valve stages 2
Lock-out type Volatile
Lock-out reset Remove mains supply for > 5 seconds
Or via the front panel reset switch (press for at least 2s)
Or via remotely mounted reset switch (press for at least 2s)
Purge time (Tp) 12s +/- 10%
Safety time (Ts) 6s +/- 10%
Number of ignition attempts 1
Flame sensitivity - detect >1.5µA
Flame sensitivity – drop-out <1µA
Flame pull-in time (PIT) < 1sec
Flame drop-out-time (DOT) < 1sec
Status Indicators/Switches Flame LED (Blue)
(refer to Installation Instructions Lockout LED (Red)
for operation) On/Standby LED (Green/Red)
Lockout Reset front panel switch
On/Standby front panel switch
Page 3 of 3
3G-CBM-04714