Datasheet Content
NEW! Ready to use
delivery method.
Compressor Burnout Acid Neutralizer
• Quick & easy to inject
• Disposable injector
• Safe for all oils
• Compressor parts safe
• Contractor preferred
• Same proven, chemical formulation
A quick & unique solution
to removing and preventing
acid buildup
in A/C and
refrigeration
systems.
Acid-Away® PRO Compressor Burnout Acid Neutralizer
Application • Chemical treatment for
Code Description Qty.
use in air conditioning and refrigeration
45016 Acid-Away PRO 12 systems that have experienced a burnout,
or operating systems that are showing
buildup in acid content • Acid-Away PRO
F E AT U R ES quickly circulates throughout the system
• Quick & easy to inject and chemically neutralizes acids that are
• Disposable injector always left in air conditioning or refrigeration
• Compressor parts safe systems after a burnout occurs • Once
• No harmful effects neutralized, the acid can no longer continue
developing corrosion impeding it from
• Tested to ASHRAE standards
causing another burnout to the system
86-1983 & 97-1989 by premier
independent testing institute Recommended for • Air conditioning and
refrigeration systems • Safe for all oils •
Acid-Away may be used in either hermetic
or semi-hermetic compressors that operate
with standard CFC or HCFC refrigerants
Disposable
Installs Using Cartridge
Standard HVAC
Manifold
High Visibility
Packaging For
Easy ID
Maximum operating
pressure is 600psi
Copper/Brass High
Pressure Cartridge Connects To Standard
1/4" Service Ports
Low Loss
Fitting
Acid Level Dosage
Light 1.5 oz of Acid Away PRO for each 64 oz of compressor oil volume
Medium 1.5 oz of Acid Away PRO for each 48 oz of compressor oil volume
Heavy 1.5 oz of Acid Away PRO for each 24 oz of compressor oil volume
This product can expose you to chemicals including Lead, which is known to the State of California
to cause cancer, birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov
RectorSeal ® • 2601 Spenwick Drive - Houston, TX 77055 • 800-231-3345 • rectorseal.com
RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its affiliates or its licensors and are protected by copyright, trademark and other intellectual property laws,
and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice. © 2020 RectorSeal. All rights reserved. R50113 0520
Acid Away® PRO Instructions Continued: SEE APPLICATION INSTRUCTIONS
Application Instructions: PRIOR TO USE. FOR CHEMICAL
EMERGENCY, SPILL, LEAK, FIRE,
RED
Installation to be preformed YELLOW EXPOSURE OR ACCIDENT, CALL
with standard HVAC manifold, CHEMTREC - DAY OR NIGHT
by a licensed A/C Technician. 1-800-424-9300.
1.) System keeps running in PRO
PRO CONTAINS: Refrigeration Oil.
cooling mode while injecting PRECAUTIONS: May be harmful
Acid Away PRO into system. if swallowed or inhaled. May
cause eye and skin irritation.
2.) Connect Acid Away PRO Keep away from heat, sparks
injector’s low loss fitting to 4.) Briefly open and close and flames. Use with adequate
the low pressure service port manifold high side valve three ventilation. Wash after
(i.e. the suction side). times to allow refrigerant to handling. FIRST AID: For any
flow through Acid Away PRO overexposure, get immediate
PRO injector. medical attention after first
aid is given. Eyes - Flush 15
minutes with clean water. Skin
RED - Wash with soap and water.
Inhalation - Remove to fresh
air. Ingestion - Only if consci-
ous, give large amounts of
water. DO NOT INDUCE
3.) (A) Ensure both valves on VOMITING. FIRE AND SPILLS:
manifold gauge set are For fire, use water fog, CO₂
closed. (B) Connect high foam or dry chemicals to
pressure (red) hose of mani- 5) With manifold closed, wait extinguish. For spills, shut off
fold to the high pressure one minute for charging hose ignition sources ventilate
service port (i.e. the liquid and Acid Away PRO injector to confined areas and wipe up
side). (C) Barely thread the equalize to suction pressure. with absorbent materials to
middle manifold (charging/ prevent footing hazard.
yellow) hose to the male Disconnect charging hose STORAGE AND HANDLING:
fitting of Acid Away PRO from Acid Away PRO injector. Store in cool, well ventilated
injector. Do not thread to area. Keep container upright
the point of depressing the Disconnect Acid Away PRO and tightly closed. Do not
Schrader core. (D) For best injector from suction service reuse empty container. KEEP
results raise the Acid Away port. Discard or recycle empty OUT OF REACH OF CHILDREN.
PRO canister above the injector. Run air conditioner
service port. (E) Briefly crack for at least 30 minuets to FOR ADDITIONAL INFORMATION,
open manifold high side allow product to fully circulate. REFER TO SAFETY DATA SHEET.
valve to purge air out of the
hose, close manifold high NOTE: If the system is low on
side valve; while quickly refrigerant, you may also use Manufactured by RectorSeal
tightening the charging hose a refrigerant tank to push 2601 Spenwick Drive,
fitting to the inlet fitting on into system. Houston, TX
the injector. 77055-1035, USA
rectorseal.com
Product Code No. 45016